Applications
Motor protection
 
Transformer protection
 
Gensets protection
 
Heating equipments protection
 
Ineffective cooling
 
Blocked ventilation
 
Overloads
 
Worn bearings
 
Features
Up to three RTD inputs
 
1mA analogue output
 
Three adjustable set points
 
Internal differential
 
LED trip indication
 
Automatic reset
 
Three single-pole relay contacts
 
Product Function
The Rishabh temperature trip relay has been designed to monitor three separate temperature zones in large electric motors, transformer winding or any temperature conscious equipment such as process lines gas turbines or engine driven generating sets, using Resistance Temperature Detectors (RTDs). The highest of three temperatures is automatically selected and a 0 to 1 milliamp output signal produced. Yellow LEDs are fitted to show which of three sensors is at the highest temperature. The output signal is compared internally with the voltage from up to three set point potentiometers and the difference fed to trigger relay circuits. Red LEDs are used to indicate relay energised. Single pole changeover relay are provided for each set point. In a typical installation the three set points would be set to trip on increasing temperature, in the following sequence :
1. Initiate cooling/ reset if effective
2. Bring up alarm/ reset if action and cooling effective
3. Shut down