Applications
Features
Product Function
The Rishabh temperature trip relay has been designed to monitor three separate temperature zones in large electric motors, transformer winding or any temperature conscious equipment such as process lines gas turbines or engine driven generating sets, using Resistance Temperature Detectors (RTDs). The highest of three temperatures is automatically selected and a 0 to 1 milliamp output signal produced. Yellow LEDs are fitted to show which of three sensors is at the highest temperature. The output signal is compared internally with the voltage from up to three set point potentiometers and the difference fed to trigger relay circuits. Red LEDs are used to indicate relay energised. Single pole changeover relay are provided for each set point. In a typical installation the three set points would be set to trip on increasing temperature, in the following sequence :
1. Initiate cooling/ reset if effective
2. Bring up alarm/ reset if action and cooling effective
3. Shut down
|