Global Energy Efficiency Solution Company
Rishabh Instruments Limited
Touch Screen - Rish Master 3440i

Touch Screen - Rish Master 3440i

Touch Screen - RISH Master 3440i is powerful compact monitoring devices for accurate and reliable measurement of important electrical parameters in 3 phase and single phase Network & replaces the multiple analog panel meters. 

User selectable CT Secondary 5A/1A

The secondary of external Current Transformer (CT) can be programmed on site to either 5A or 1A locally by entering into Programming mode or remotely via MODBUS (Rs485)

User selectable PT Secondary

The secondary of external potential Transformer (PT) can be programmed on  site  locally  by  entering  into  programming  mode  or  remotely  via MODBUS (RS485)

User selectable 3 phase 3W or 4W unbalanced network

User can program on site the network connection as either 3 Phase 3 Wire or 4 Wire locally    by entering into Programming mode or remotely via MODBUS (RS485). For single phase applications,  single phase version is available.

Low back depth

The instrument has very low back depth (behind the panel) of less than 80 mm in spite of optional features like pulse output

Onsite selection of Auto scroll / Fixed Screen

User can set the display in auto scrolling mode or fixed screen mode can be programmed locally by entering into Programming mode or remotely via MODBUS (RS485).

Phase reversal indication

The instrument can detect wrong phase sequence or failure of one of the input voltages and displays “phase” error message.

Energy measurement (Import and Export)

Active energy (kWh), Reactive energy (kVArh), Apparent energy (kVAh) & Ampere Hour (kAh). Any of the parameters can be freely assigned to 2 optional pulse outputs.

True RMS measurement

The instrument is capable of True RMS measurement with an impact of harmonics up to 15th order

User selectable Low Current suppression (below 30 mA)

User can suppress the readings below 30 mA in the current measurement by onsite programming if required.

Min Max storage of parameters possible

The instrument stores minimum and maximum values for System Voltage  and  System  Current.  Every  40  sec  minimum  and  maximum readings are updated.

Number of parameters measured: more than 46

The instrument measures more than 46 electrical parameters of 3 Phase network.

Parameter Screen recall

In case of power failure, the instrument memorizes the last displayed screen. The displayed screen will get memorized only if user keeps this screen for minimum 40 sec duration before power failure for fixed screen mode.

Phasor Diagram

Pictorial representation of all 3 Phases (Voltage & Current) in terms of vectors.

Wave Form

Pictorial representation of all  3 phases    Current & voltage in terms of sinusoidal waveform.

Total Harmonic Distortion (THD)

The instrument can measures per phase (%) THD of voltage and (%) THD of current.

Energy Count storage

In case of power failure, the instrument memorizes the last energy count. 

Hour Run, ON Hour, Number of Interruptions

Hour run records the number of hours load is connected. ON Hour is the period for which the auxiliary supply is ON. Number of Interruptions indicates the number of times the Auxiliary Supply was interrupted.

Optional MODBUS (RS485) Output

The optional MODBUS output enables the instrument to transmit all the measured parameters over standard MODBUS (RS485).

User Assignable Registers for MODBUS

Customer can assign MODBUS register address as per his need for faster response time. 

Optional Pulse Output ( 2 Relay output / Limit switch )

The instrument can be programmed as Pulse output or Limit Switch. 

Pulse Output: The optional pulse output is a potential free, very fast acting relay contact which can be used to drive an external mechanical counter for energy measurement.

Limit switch: The instrument will trip the one or two relays if the programmed parameter exceeds the programmed High & Low Limits.

Configuration of the Instrument via MODBUS

The  instrument  settings  can  be  configured  locally  by  entering  into Programming mode or remotely via MODBUS (RS485)

Note: The MODBUS communication parameters can only be set locally by entering into the Programming mode.

Ethernet Interface (Modbus TCP/IP Protocol)

The optional Ethernet Interface output transmit all the measured parameters on Modbus TCP/IP. Also user can configure their instrument via Ethernet Interface.

Optional Analog Outputs (2 Outputs)

2  Analog  outputs  can  be  programmed  from  a  list  of  input parameters.

Enclosure Protection for dust and water

conforms to IP 54 (front face) as per IEC60529

Compliance to International Safety standards

Compliance to International Safety standard IEC 61010-1- 2001

EMC Compatibility

Compliance to International standard IEC 61326

Related products

People Also Look For

Crafted with precision and reliability, our products ensure top performance and durability. Experience excellence with every measurement.

View All
Elapsed Time Meter

Rish ED21X1

RISH ED21X1 measures important electrical parameters in 1Ph 2 Wire Networks.The meter is available in 100A Max.current measurement range on direct connection.The instrument has 2 SO outputs and 1DI for tariff counter.It displays parameters on bright LCD, Impulse LED for energy monitoring.

Elapsed Time Meter

Rish ED43XX

RISH ED43XX supports 3Ph direct connection Max.100A saving money and reducing the hassle of connecting additional CTs.With remote monitoring and setting there is SO output along with MODBUS port.Suitable for measuring energy usage in utility, industrial, and EV charging system applications.

Elapsed Time Meter

Rish ED1111

Rish ED1111 supports a direct connection max. 45A, saving money & reducing the hassle of connecting additional CTs. With remote monitoring & setting, there's a SO o/p along with a MODBUS port available.

Elapsed Time Meter

Rish LM 1360 -Load Manager (RJ12)

RISH LM1360 measures important electrical parameters in 3ph4W,3ph3W & 1ph2W Network. It measures electrical parameters like energy, power & all basic parameter. The instrument has 2 optional o/p. It can be configured as pulse o/p for energy measurement, limit o/p, timer function & RTC relay.

Elapsed Time Meter

Rish Delta Power NX

The Delta Power NX is a range of Three-line, three-phase digital panel meters for reliable and accurate true-RMS measurement of electrical parameters (voltage, current, power, frequency, power factor, demand parameters etc).

Elapsed Time Meter

Rish Delta VAF NX

The Delta VAF NX is a range of Multi-function meter for reliable and accurate measurement of AC parameters (voltage, current, frequency, power factor) for industrial and commercial applications. MFM provides true RMS measurement for AC parameters.

Elapsed Time Meter

Rish Delta Energy NX

RISH Delta Energy NX measures important electrical parameters in 3phase 4wire, 3phase 3wire, 1phase 2wire and 1phase 3wire network. It measures electrical parameters like Active / Reactive / Apparent energy, power and all basic parameter.

Elapsed Time Meter

DIN Rail - RISH MD1340 (RJ12 - 100mA)

RISHMD1340 measures important electrical parameters in 3 phase 4 wire,3 phase 3 wire & 1 phase 2 wire Network. It displays many parameters at a glance. The instrument has two optional 2 DO or 1SO. This instrument also has two optional digital inputs